Control Box has No Power - Check and Verify power at terminal block using a multimeter. Remove two fuses and check and verify ampacity.
All Motors go in the wrong direction - Change Direction 1 and Direction 2 at the motor terminals on the premier remote control printed circuit board.
Some motors go in the wrong direction. Identify the motor(s) that are moving in the wrong direction.
Option 1 (recommended) - Change the motor direction 1 and direction 2 at the motor terminals on the premier remote control printed circuit board.
Option 2 - Change leads at motor by swapping wires identified with “*”. On “T” motors this is T5 and T8. On spade motors, this is typically motor red and motor black. Please see the wiring diagram in appendix B.
Front Panel is not responding or is not backlit - Refer to Section 3. Ensure the front panel ribbon is seated into the front panel terminal on the Printed Circuit Board.